Evaluation of Alternate Equipotential Bonding Means

Full Report

Evaluation of "Alternate Equipotential Bonding Means" to Reduce Voltage Gradients in Pool Areas (PDF, 2 MB)

All Fire Protection Research Foundation reports can be downloaded for free. Printed copies are $50, except where otherwise noted. If all reports in a subject category are requested, a 20% discount applies.

Please pre-pay by check or money order to the The Fire Protection Research Foundation. You may also pay using VISA, Mastercard or American Express. E-mail the Foundation or call +1 617 984-7443.

Fire Protection Research Foundation report: "Evaluation of 'Alternate Equipotential Bonding Means' to Reduce Voltage Gradients in Pool Areas"
Author: Jens Schoene, Ph.D., EnerNex LLC, Knoxville, TN
Date of issue: October 2011

Foreword

A common approach to reduce the voltage gradients in a pool area is by using a single buried #8 AWG copper conductor following the perimeter surface around the pool. This is identified as an alternate means of perimeter equipotential bonding for permanently installed swimming pools and spas according to 680.26(B)(2)(b) of the 2011 edition of NFPA 70®, National Electrical Code® (NEC®).

This arrangement is intended to provide a 60 Hz ac voltage gradient protection to prevent injury or death, but questions exist on its effectiveness. This includes defining nominal "safe" levels based on differentiating between conditions that are tolerable (i.e., benign or an irritant) versus dangerous, and evaluating nominal performance of the conductor with respect to these levels.

This project provides information that clarifies the effectiveness of "alternate equipotential bonding means" for swimming pools and similar installations. A specific focus is provided on the impact on voltage gradients from the use of a single #8 AWG copper ring installed according to the requirements of 680.26(B)(2)(b) of the NEC.

The Research Foundation expresses gratitude to the report author Jens Schoene, Ph.D., along with Vadim Zheglov, Sharanya Jaganathan, and other members of his research team, all of whom are with EnerNex LLC located in Knoxville, Tennessee. During this research effort, significant input and guidance was provided by the Electric Power Research Institute through Douglas Dorr and others. In addition, the Research Foundation appreciates the guidance provided by the Project Technical Panelists, and all others that contributed to this research effort. Special thanks are expressed to the National Fire Protection Association (NFPA) for providing the project funding through the NFPA Annual Code Fund.